gauge displays value close to 0 when disconnected, potentially dangerous for pump #13

Open
astechow opened this issue May 26, 2020 · 2 comments

Comments

@astechow
Copy link

The absolute pressure gauge controller displays values around 1 Torr when disconnected from the gauge. If "pumpdown and refill" is chosen in this state, the valve to the pump will open, potentially damaging it. Is there a way to detect a malfunction of the controller?

@jameslterry
Copy link
Collaborator

Is the pressure reading always within some small range around 1 Torr under this disconnected condition? If so, then perhaps we could do a check for this constant pressure reading being sustained for (say ) 3 seconds before starting or not starting the "pumpdown and refill" sequence.

@astechow
Copy link
Author

I would need to check this. I don't know if this depends on the calibration of the gauge as well which is done on the controller if I recall correctly. It definitely fluctuates, but maybe to a much smaller degree than when connected to the gauge