Skip to content

ClientLN

Davood Sooran edited this page Feb 16, 2024 · 2 revisions

A ClientLN is one of the three elements that describe connections between IEDs in a SCL file.

HowTo connect Report with ClientLNs

OpenSCD allows you to connect ReportControl via ClientLN. The starting point is the IED in the Substation editor.

alt text
  • Click on an IED.
  • Click on the Add connection button.
  • The ClientLN wizard opens.
  • On the left-hand side, you can select the ReportControl element(s) in the project.
  • On the right-hand side, you can see all logical nodes in the receiving IED (client).
  • All so-called client logical nodes - logical nodes allocated to AccessPoint are sorted to be on top.
  • LN0 elements are sorted to be at the bottom.
  • Click on CONNECT.

grafik

NOTE: If ClientLN connections are already present in the Report Control block, the wizard does not close on CONNECT

NOTE: If the RptEnabled max attribute is smaller or equal to the ClientLN, a connection is not possible. The ReportControl on the right-hand side is disabled.

TIP: You can filter for several terms at the same time. The space between terms acts as a logical AND.